Product Detail

8.7/15 kV XLPE Insulated, Flat Steel Wire Armored, Three Core Cables with Copper Conductor

Code

YXC8VZ3V-R, N2XSEYFGY

R: Stranded Rigid Conductor

Standards

IEC 60502 - 2, VDE 0276 - 620

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded copper conductors

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Filler

8. Inner sheath

9. Galvanized flat steel wire

10. Galvanized steel tape

11. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

8.7/15 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Delivery

Length

DC Conductor

Resistance at

20 0C Max

Operation Inductance

(approx.)

Operation

Capacitance

(approx.)

Current Carrying Capacity

(A)

mm2

mm

kg/km

m

Ohm/km

mH/km

µF/km

In ground

at 20oC

In air

at 30oC

3x35/16

57.0

5110

500

0.524

0.397

0.160

178

173

3x50/16

60.5

6000

500

0.387

0.377

0.175

210

206

3x70/16

64.5

7000

500

0.268

0.356

0.196

256

257

3x95/16

68.5

8250

500

0.193

0.339

0.218

307

313

3x120/16

72.5

9450

500

0.153

0.325

0.240

349

360

3x150/25

76.0

10750

250

0.124

0.315

0.258

392

410

3x185/25

80.0

12350

250

0.0991

0.305

0.280

443

469

3x240/25

87.0

14800

250

0.0754

0.292

0.315

513

553

3x300/25

92.0

17250

250

0.0601

0.284

0.343

576

635

3x400/35

100.0

21300

250

0.0470

0.273

0.385

650

731

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources

Get a copy of brochure on Cu Conductor, XLPE Insulated, FSW Armored, 3-Core MV Cables (8.7/15 kV).