Product Detail

0.6/ 1kV PVC Insulated, Concentric Conductor Screen, Multi-Core Cables with Copper Conductor

Code

YVCV-U, YVCV-R, CU/PVC/SC/PVC, NYCY

U: Solid Conductor

R: Stranded Rigid Conductor

Standards

IEC 60502-1, VDE 0276-603

Application

Indoor installations; in cable ducts; outdoor and underground at power stations; in industrial plants and switching stations as well as local supply systems where high degree of protection is required. In case of mechanical damage, screen prevents hazardous effects of power leakage over surrounding area.

Construction

1. Solid or stranded copper conductors

2. PVC insulation

3. Filler

4. Concentric copper wire

5. Copper tape as binder

6. Polyester tape

7. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

70 oC

Max. short circuit temperature    

:

160 oC (Max. 5 sec.)

Rated voltage

:

0.6 / 1kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

 

Nominal

Overall

 

 

DC Conductor

Current Carrying Capacity

 

Cross-

Diameter

Net Weight

Delivery

Resistance at

In Ground at

In Air at

 

Section

(approx.)

(approx.)

Length

200C Max

200C

300C

 

mm2

mm

kg/km

m

Ohm/km

A

A

 

3x1,5/1,5

14.0

240

1000

12.1

26

18.5

 

3x2,5/2,5

15.0

300

1000

7.41

34

25

 

3x4/4

17.0

420

1000

4.61

44

34

 

3x6/6

17.5

530

1000

3.08

56

43

 

3x10/10

20.0

730

1000

1.83

75

60

 

3x16/16

22.0

1000

1000

1.15

98

80

 

3x25/16

25.5

1400

1000

0.727

128

106

 

3x35/16

27.5

1750

1000

0.524

157

131

 

3x50/25

31.0

2350

1000

0.387

185

159

 

3x70/35

35.0

3200

1000

0.268

228

202

 

3x95/50

39.5

4300

1000

0.193

275

244

 

3x120/70

43.5

5350

500

0.153

313

282

 

3x150/70

47.5

6450

500

0.124

353

324

 

3x185/95

52.0

8000

500

0.0991

399

371

 

3x240/120

59.5

10350

250

0.0754

464

436

 

3x300/150

66.5

12850

250

0.0601

524

481

 

3x400/185

78.0

17300

250

0.0470

600

560

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7