Product Detail

3.6/6 kV XLPE Insulated, Three Core Cables with Aluminum Conductor

Code

YAXC8V-R, NA2XSEY, AL/XLPE/CTS/PVC

R: Stranded Rigid Conductor

Standards

IEC 60502-2, VDE 0276-620, BS 6622

 

Application

Characterized with low dielectric loss. Used in energy networks where load may change suddenly. Laid in residential or industrial areas, and underground in ducts.

Construction

1. Stranded aluminum conductor

2. Inner semi-conductive layer

3. XLPE insulation

4. Outer semi-conductive layer

5. Semi-conductive tape

6. Copper screen

7. Filler

8. PVC outer jacket

Technical Data

 

 

Max. operating temperature       

:

90 oC

Max. short circuit temperature    

:

250 oC (Max. 5 sec.)

Rated voltage

:

3.6/6 kV

Min. bending radius

:

15 x D

(D: Cable outer diameter)

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal

Cross

Section

Overall

Diameter

(approx.)

Net

Weight

(approx.)

Delivery

Length

DC Conductor

Resistance at

20 0C Max

Operation Inductance

(approx.)

Operation

Capacitance

(approx.)

Current Carrying Capacity

(A)

mm2

mm

kg/km

m

Ohm/km

mH/km

µF/km

In ground

at 20oC

In air

at 30oC

3x35/16

42.0

2050

1000

0.868

0.352

0.229

-

-

3x50/16

45.0

2400

1000

0.641

0.336

0.255

160

150

3x70/16

48.5

2850

1000

0.443

0.318

0.288

199

191

3x95/16

53.0

3400

1000

0.320

0.303

0.324

238

236

3x120/16

57.0

4000

1000

0.253

0.292

0.359

275

273

3x150/25

60.5

4500

1000

0.206

0.284

0.388

307

313

3x185/25

64.5

5150

500

0.164

0.276

0.424

349

360

3x240/25

71.0

6300

500

0.125

0.267

0.469

410

426

3x300/25

77.5

7600

500

0.100

0.263

0.486

460

528

3x400/35

86.0

9400

500

0.0778

0.257

0.521

520

564

 

 

 

 

 

 

 

 

 

 

NOTE                        : Current carrying capacities are valid under the following conditions.

In ground                 : 200C; buried in 70 cm depth; soil thermal resistivity 1 K.m/W; load factor 0.7

In Air                        : 300C; load factor 1.0

***                          : Flat formation; clearance between cables in air = 1 x cable outer diameter; in ground = 7cm

***                           : Trefoil formation

Number of System    : 1

Resources